Skip to content

Earth Fault Loop Impedance Calculator — BS 7671

Calculate total earth fault loop impedance (Zs) from Ze and R1+R2 measurements. Check compliance against BS 7671 18th Edition (including Amendment 4, 2026) maximum values for automatic disconnection of supply.

Measured at the origin of the installation

Combined line and CPC resistance

How We Calculate This

This calculator determines whether the earth fault loop impedance at a point in a circuit is low enough for the protective device to disconnect within the required time specified in BS 7671 18th Edition.

The calculation

Step 1: Total earth fault loop impedance is calculated as Zs = Ze + (R1+R2), where Ze is the external earth fault loop impedance and R1+R2 is the combined resistance of the line conductor (R1) and circuit protective conductor (R2).

Step 2: The measured R1+R2 value is corrected for conductor operating temperature using the correction factor (230 + operating temp) / (230 + ambient temp). For thermoplastic cables at 70 degrees Celsius measured at 20 degrees Celsius, the factor is 1.20.

Step 3: The corrected Zs is compared against the maximum permitted value from BS 7671 Table 41.2 (fuses) or Table 41.3 (circuit-breakers) for the specific protective device type and rating. For Type B and Type C circuit-breakers the maximum Zs is a single value set by the instantaneous magnetic trip (5×In for Type B, 10×In for Type C), so it is the same whether 0.4-second or 5-second disconnection is required. Type D circuit-breakers are different: because their magnetic trip is set higher (20×In), Table 41.3 lists a higher max Zs at 5 seconds than at 0.4 seconds (for example a 32A Type D allows 0.34 Ω at 0.4s but 0.68 Ω at 5s). This calculator applies the 0.4-second value, which is the correct and conservative limit for the final circuits it offers.

Disconnection times (TN systems, BS 7671 Regulation 411.3.2.2)

  • 0.4 seconds: Required for final circuits up to 63A with one or more socket-outlets, and final circuits up to 32A supplying only fixed connected equipment. (The 18th Edition raised the socket-outlet threshold from the 32A used in the 17th Edition.)
  • 5 seconds: Permitted for distribution circuits.

Maximum Zs values and disconnection times are unchanged by BS 7671:2018+A4:2026 (Amendment 4, published 15 April 2026, mandatory from 15 October 2026), so the figures above remain current.

Frequently Asked Questions

Related Guides & Answers

Was this calculator helpful?

Last updated: June 2026

Verified against UK standards · estimates only, confirm with your supplier.