Skip to content

Zs Earth Fault Loop Impedance Calculator

Calculate total earth fault loop impedance (Zs) from Ze and R1+R2 and validate against BS 7671:2018+A4:2026 Table 41.3 maximum Zs values for BS EN 60898 circuit-breakers and BS EN 61009-1 RCBOs (Types B/C/D) — using either temperature correction or the GN3 0.8 rule of thumb (one method, never both).

Measured at origin with main earth disconnected

Line + CPC resistance at test (ambient) temperature

Safety notice

Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.

How We Calculate This

This calculator determines total earth fault loop impedance from the measured components:

Measured Zs = Ze + (R1 + R2)

It then checks Zs against the BS 7671 Table 41.3 maximum for your circuit-breaker or RCBO (BS EN 60898 / BS EN 61009-1, Types B/C/D), using one of two equivalent GN3 methods to bridge the gap between your cold test measurement and the hot tabulated limit:

  • Temperature correction (Method 2): correct R1+R2 up to operating temperature, then compare against 100% of the tabulated maximum: Corrected Zs = Ze + (R1 + R2) × Ct, where Ct = [1 + 0.004 × (Operating − 20)] ÷ [1 + 0.004 × (Ambient − 20)] (≈ ×1.20 for a 20°C test and a 70°C PVC conductor; the 0.004/°C copper coefficient is referenced to 20°C per BS 7671 Appendix 4).
  • 0.8 rule of thumb (Method 1): leave the measured Zs uncorrected and compare it against 0.8 × the tabulated maximum (GN3 Appendix A2).

Do not combine the two — both account for the same rise in conductor resistance, so applying them together double-counts and can fail a compliant circuit. Prospective fault current is taken from the measured Zs (Ipf = U0 ÷ Zs, U0 = 230 V).

BS 7671 Maximum Zs Values

  • Type B MCBs: Trip at 3-5 × In — highest Zs allowed
  • Type C MCBs: Trip at 5-10 × In — half the Zs of Type B
  • Type D MCBs: Trip at 10-20 × In — quarter the Zs of Type B
  • 0.4s disconnection: Required for final circuits up to 63A (Table 41.1)
  • 5s disconnection: Permitted for distribution circuits

Frequently Asked Questions

Was this calculator helpful?

Last updated: June 2026

Verified against UK standards · estimates only, confirm with your supplier.