Skip to content

Consumer Unit Sizing Calculator — How Many Ways Do I Need?

Calculate the right consumer unit size for your property based on BS 7671 18th Edition. Includes spare ways for future expansion.

20% recommended for future expansion

Cooker circuit

32A dedicated circuit for electric cooker

Electric shower circuit

45A dedicated circuit for an electric shower up to 9.5kW (10mm² T&E)

Immersion heater

16A dedicated circuit

EV charger

32A dedicated circuit for a 7.4kW charger, normally a Type A RCBO (BS 7671 Section 722 / IET Code of Practice for EV Charging)

Intruder alarm / CCTV

6A dedicated circuit

Outdoor socket / lighting

16A dedicated circuit

Underfloor heating

16A dedicated circuit

Smoke / heat detectors

6A dedicated circuit — required by Building Regs

How We Calculate This

This calculator determines the consumer unit size you need by counting all required circuits for your property and adding spare ways for future expansion, following BS 7671 18th Edition guidelines.

The formula

Total ways = Number of circuits + Spare ways (min 20% or 2 ways)

The calculator then rounds up to the nearest standard single-row domestic consumer unit size sold in the UK: 6, 8, 10, 14, 16, or 20 ways. Above 20 ways you move to a split-load or dual-row board.

Standard UK circuit MCB ratings

  • Lighting circuits: 6A Type B MCB
  • Ring main (sockets): 32A Type B MCB
  • Cooker circuit: 32A Type B MCB
  • Electric shower (up to 9.5kW): 45A Type B MCB with 10mm² cable (9.5kW ÷ 230V = 41.3A; 40A only suits showers up to ~8.5kW)
  • Immersion heater: 16A Type B MCB
  • EV charger (7.4kW): 32A device, normally a Type A RCBO (BS 7671 Section 722)
  • Smoke detectors: 6A Type B MCB

Frequently Asked Questions

Was this calculator helpful?

Last updated: February 2026

Verified against UK standards · estimates only, confirm with your supplier.