TradeCalculator.co.uk
House Rewiring Calculator — Circuits, Cable & Consumer Unit
Estimate the number of circuits, cable lengths, consumer unit size and accessory counts for a full house rewire based on BS 7671.
Total bedrooms in the property
Including ground floor
Additional Requirements
Adds a dedicated 40/45A circuit and 15m of 10mm² T&E
Dedicated 32A radial. 6mm² T&E up to ~30m; the result steps to 10mm² for longer runs (volt drop plus derating in insulation, BS 7671 Section 722 / Table 4D5)
Dedicated radial circuit per zone
Dedicated circuit for smart home equipment
How We Calculate This
This calculator estimates the electrical requirements for a full house rewire based on property type, size and additional requirements. It uses typical UK domestic installation practices and BS 7671 18th Edition guidelines.
Base specification (3-bed semi)
- Ring mains: 2 (ground floor + first floor)
- Lighting circuits: 3 (one per floor plus the landing)
- Cooker circuit: 1 (6mm² T&E, 32A MCB)
- Smoke-alarm supply: 1 dedicated way for the interlinked BS 5839-6 system
- Consumer unit: circuits + your chosen spare ways (default 2); a bare 3-bed comes to ~9 ways, rising to 11-13 once an electric shower, EV charger or other dedicated circuits are added
- 2.5mm² cable: ~150m (sockets)
- 1.5mm² cable: ~100m (lighting)
Adjustments
- Additional bedrooms and floors increase circuit count and cable length
- Electric shower adds a dedicated 40/45A circuit and ~15m of 10mm² T&E
- EV charger adds a dedicated 32A radial (standard 7kW home charger). The cable is 6mm² T&E up to roughly 30m; the result steps up to 10mm² for longer runs. The 30m step-up reflects the more onerous of two BS 7671 limits — voltage drop (6mm² = 7.3 mV/A/m, Table 4D5; the 5% / 11.5V limit is reached near 49m but good practice keeps an EV charger nearer 3%) and current-carrying capacity once the cable runs through wall voids or thermal insulation (Reference Method 101/102, Section 722), where 6mm² derates well below its 47A clipped-direct rating
- Underfloor heating and smart home systems add dedicated circuits
Smoke detectors (BS 5839-6)
A rewire triggers minimum Grade D LD2 requirements: mains-powered, interlinked smoke alarms in every circulation space (hallways and landings), a heat alarm in the kitchen, and an alarm in the principal habitable room. The detector count shown here is an indicative minimum based on floor count — confirm it against the actual circulation spaces and high-risk rooms in your property, as LD2 is driven by layout, not a fixed multiple of floors.
Frequently Asked Questions
Related Calculators
Cable Length Calculator
Estimate total cable length needed from your floor plan dimensions.
Consumer Unit Sizing Calculator
Calculate how many ways your consumer unit needs for your property.
Electric Shower Circuit Calculator
Calculate cable size, MCB rating and voltage drop for electric shower circuits.
Outdoor Lighting Circuit Calculator
Calculate outdoor lighting circuits with SWA cable sizing and earth rod for TT systems.
Part P Electrical Notification Calculator
Determine Part P notification requirements by electrical work type.
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.