Lux Level Calculator — CIBSE Lumen Method

Calculate the number of light fittings needed to hit recommended lux levels using the lumen method. Workplace targets follow BS EN 12464-1:2021 (CIBSE/SLL Code for Lighting 2022). Covers offices, warehouses, retail, and domestic rooms.

Internal room length

Internal room width

Floor to ceiling

Safety notice

Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.

How We Calculate This

This calculator uses the CIBSE lumen method to determine the number of light fittings required to achieve the recommended illuminance level.

Lumen Method Formula

N = (E × A) ÷ (F × UF × MF)

Where E = lux, A = area (m²), F = lumens per fitting, UF = utilisation factor, MF = maintenance factor

Room Index

K = (L × W) ÷ (Hm × (L + W))

  • K < 1.0: Small or tall room — low UF
  • K = 1.0-2.0: Typical office/classroom
  • K > 3.0: Large open-plan — high UF