TradeCalculator.co.uk
Smart Meter CT Calculator
Select the correct CT ratio for smart metering based on maximum demand. Calculate secondary wiring burden, required CT VA rating, and number of CTs for single and three-phase supplies.
Peak demand. Treated as kVA (PF = 1) — the conservative sizing convention; enter your kVA if PF is low
CT-to-meter loop: ≤10m → 2.5mm², 10–20m → 4mm², >20m → 6mm²
Three-phase line voltage
Meter's VA consumption
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator selects the appropriate CT ratio based on maximum demand and calculates the secondary wiring burden to ensure metering accuracy.
Key Calculations
Max current = kW × 1000 ÷ (V × √3) (three-phase)
Wire burden (VA) = I² × R = 25 × (2 × L × ρ)
CT Selection Rules
- Primary: Next standard size at or above max-demand current. This minimum leaves no headroom — add 25–50% for load growth (target ~60–80% of rated)
- Secondary: 5A standard (1A for long runs)
- Accuracy: Class 0.5S for UK billing/half-hourly metering (specified 1–120% of rated), Class 1.0 for monitoring (BS EN 61869-2)
- Burden: Total secondary burden (wire + meter) must not exceed the CT's rated VA
- Wiring: 2.5mm² up to 10m, 4mm² 10–20m, 6mm² over 20m
Frequently Asked Questions
Pick the next standard primary at or above your maximum-demand current — but ideally with some headroom. A 200A demand sized to 200/5A CTs runs the CT at 100% of rated, which is the top of the accuracy window with no margin for growth; many installers size up (e.g. 250/5A) so the CT runs at the more accurate ~60–80% of rated and has spare capacity. Standard ratios: 50/5, 100/5, 150/5, 200/5, 250/5, 300/5, 400/5, 500/5, 600/5, 800/5, 1000/5A. Don't grossly oversize either — a 1000/5A CT on a 100A supply reads only 10% of rated and is inaccurate at low load, because metering CTs are specified 5–120% of rated primary (Class 0.5S from 1%) per BS EN 61869-2. Use our Maximum Demand Calculator to determine your peak current.
Single-phase supply: 1 CT on the line conductor. Three-phase 3-wire (no neutral, e.g., motor supplies): 2 CTs on any two phases (Blondel's theorem). Three-phase 4-wire (with neutral): 3 CTs, one on each phase. The meter uses the CT signals to calculate power. Half-hour data meters typically use 3 CTs for 4-wire supplies to capture all phase power and reactive components accurately.
Per IEC 61869-2 (BS EN 61869-2), a Class 0.5 CT holds a ratio error within ±0.5% at rated current, with accuracy specified across 5% to 120% of rated primary current (test points 5/20/100/120%). UK fiscal and half-hourly billing metering now generally requires the 'S' (special) variant — Class 0.5S — which is specified down to 1% of rated current, so it stays accurate at low load (Elexon Codes of Practice, e.g. CoP5). Plain Class 0.5 suits general metering, Class 0.2/0.2S high-accuracy revenue metering on large supplies, and Class 1.0 sub-metering and energy monitoring (non-billing). Don't pay for a higher class than the application needs.
CT burden is the total impedance of the secondary circuit — including the meter, wiring, and any other connected devices. It is expressed in VA (volt-amperes) at rated secondary current. If the actual burden exceeds the CT's rated burden, accuracy degrades because the CT core saturates. Typical meter burden is 2-5VA. Secondary wiring adds burden proportional to wire length and inversely to wire size. Total burden must not exceed the CT's VA rating (typically 5-15VA).
CT secondary wiring size depends on the distance from CTs to meter and the secondary current (usually 5A). For runs up to 10m: 2.5mm² copper is adequate. 10-20m: 4mm². Over 20m: 6mm² or larger. The wire adds burden = I² × R, where I is 5A and R is the total send+return resistance. A 20m run in 2.5mm² has R = 2 × 20 × 0.00741 = 0.296Ω, giving burden = 25 × 0.296 = 7.4VA — which may exceed the CT's rated burden. Use 4mm² instead.
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.