TradeCalculator.co.uk
Prospective Fault Current (PFC) Calculator
Calculate PSCC (line-neutral short circuit) and PEFC (line-earth fault) from measured loop impedance and verify against protective device breaking capacity per BS 7671 Regulation 434.5.1.
Line-to-neutral loop (PSC/L-N test on your tester) — determines PSCC
Line-to-earth loop (PEFC/L-E test, or Ze + R1+R2) — determines PEFC
Nominal line-neutral voltage (230V) — matches tester convention
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
Prospective fault current is calculated using Ohm's law applied to the relevant fault loop, the same way a multifunction tester does — nominal voltage divided by the measured loop impedance, with no correction factor:
PSCC = Uo / Zpn (short circuit between live conductors — line-to-neutral on a single-phase supply)
PEFC = Uo / Zs (line-to-earth fault)
Where Uo is the nominal line-to-neutral voltage (230V UK), Zpn is the line-neutral loop impedance and Zs is the line-earth loop impedance. PSCC uses the line-neutral path, not the earth path, because a short circuit is a fault between live conductors. The higher of PSCC and PEFC is recorded as the prospective fault current (IET Guidance Note 3 / NICEIC). This tool covers single-phase supplies; for a symmetrical three-phase fault, use the line-neutral impedance per phase or our cable-resistance Prospective Fault Current Calculator.
BS 7671 Requirements
- Regulation 643.7.3.201: Prospective fault current (short-circuit and earth fault) must be measured, calculated or determined at the origin and at every relevant point
- Regulation 434.5.1: Breaking capacity must be at least the prospective fault current at the point of installation
- Regulation 411.4.5: Zs must be low enough for disconnection within the required time
- Typical domestic: 6kA breaking capacity for MCBs
- Commercial: 10-25kA breaking capacity typically required
- Back-up protection: Per Regulation 434.5.1, a device with lower breaking capacity is permitted if backed up by a device with adequate capacity
Frequently Asked Questions
PSCC (Prospective Short-Circuit Current) is the current that would flow in a short circuit between live conductors — line-to-neutral on a single-phase supply — calculated as Uo divided by the line-neutral loop impedance Zpn. PEFC (Prospective Earth Fault Current) is the current that would flow in a line-to-earth fault — calculated as Uo divided by the line-earth loop impedance Zs. PSCC is normally higher than PEFC because the line-to-neutral return path has lower impedance than the line-to-earth path, so it carries the larger fault current. The higher of the two readings is recorded as the prospective fault current and checked against the breaking capacity of protective devices. See also our Prospective Fault Current Calculator for a more detailed analysis from cable resistances.
BS 7671 Regulation 434.5.1 requires that every protective device has a rated short-circuit breaking capacity not less than the prospective fault current at its point of installation. If the fault current exceeds the breaking capacity, the device may not be able to safely interrupt the fault — potentially causing an arc flash, fire, or explosion. This is a critical safety requirement verified during initial verification.
UK domestic installations typically see PSCC values between 1kA and 6kA at the origin. Supplies fed from older overhead lines may be as low as 0.8kA, while modern underground supplies in urban areas can reach 16kA or more. Most domestic MCBs and consumer units are rated at 6kA breaking capacity. If PSCC exceeds 6kA, you need devices rated to 10kA or higher, or an upstream device providing back-up protection.
For PSCC enter the line-to-neutral loop impedance (Zpn) — most multifunction testers measure this directly when you select the PSC or L-N loop test. For PEFC enter the line-to-earth loop impedance (Zs), which is the L-E loop test, or Ze + (R1+R2) at the point of interest. Do not use Ze (the external earth loop measured with the earthing conductor disconnected from the MET) for PSCC — Ze is part of the earth-fault path, not the short-circuit (line-neutral) path. Typical origin values: line-neutral loop is often a few tenths of an ohm; Ze for TN-S (cable sheath earth) = 0.35-0.8Ω, TN-C-S (PME) = 0.2-0.35Ω, TT = can be very high (1-200Ω or more).
Yes — modern multifunction testers like the Megger MFT or Metrel measure PFC directly in kA. The tester calculates it from the measured loop impedance using Ohm's law (I = Uo / Z) with the nominal voltage (230V for a 230V supply) and no correction factor — for example the Megger MFT manual shows 230V ÷ 0.13Ω = 1.77kA. This calculator follows the same convention, so the figures here match what your tester reports from the same impedance. Take the line-neutral reading for PSCC and the line-earth reading for PEFC; the higher of the two is the recorded prospective fault current.
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.