Skip to content

Prospective Fault Current Calculator — BS 7671

Calculate prospective short circuit current (PSCC) and prospective earth fault current (PEFC) from loop impedance values per BS 7671:2018+A4:2026 (18th Edition) Regulation 434.5.1.

Measured at origin of installation

One-way cable run length

Resistance per metre of line conductor

Resistance per metre of neutral conductor

Resistance per metre of circuit protective conductor

How We Calculate This

This calculator determines the maximum prospective fault current at the origin and at any point in a circuit using Ohm's law applied to the fault loop impedance, with the voltage factor Cmax = 1.10 applied per BS 7671:2018+A4:2026 Appendix 3 / IEC 60909.

Prospective fault current formula

At the origin: PSCC = Cmax × Uo / Ze, where Uo is the nominal line-to-neutral voltage (230V single phase), Cmax = 1.10 (so 230V × 1.10 = 253V) and Ze is the external earth fault loop impedance.

At any point: PEFC = Cmax × Uo / Zs, where Zs = Ze + R1 + R2 (the total line-earth loop impedance including circuit conductor resistances).

The Cmax = 1.10 factor is a conservative design upper bound: ESQCR permits the 230V supply to sit up to +10% high (253V), so the calculated fault current is the worst case. It reads roughly 10% higher than a hand-held PFC tester, which measures at the actual supply voltage with no voltage factor applied.

Breaking capacity

BS 7671:2018+A4:2026 Regulation 434.5.1 requires the rated breaking capacity of each protective device to be not less than the prospective fault current at its point of installation. A device with a lower breaking capacity is still permitted where adequate upstream (back-up) protection limits the let-through energy, or where the assembly carries a conditional short-circuit rating. The calculator compares the unconditional PSCC at the origin against the device breaking capacity.

  • MCBs to BS EN 60898: commonly 6kA, sometimes 10kA (suitable for most domestic supplies)
  • BS 88-3 HRC fuses: up to 80kA breaking capacity
  • BS 1361 Type I consumer-unit cartridge fuse: 16.5kA at 240V
  • BS 1361 / BS 88-3 Type II house-service cut-out: 33kA at 415V (ASTA-enhanced to 80kA)
  • Domestic consumer unit (BS EN 61439-3): commonly 16kA conditional rating behind a 100A BS 88-3 service cut-out

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.