TradeCalculator.co.uk
Transformer Sizing Calculator
Size a distribution transformer from load kW, apply the 80% loading rule, and determine primary/secondary currents, voltage regulation, and secondary fault level.
Maximum demand after diversity
0.85 typical for mixed loads
HV supply voltage
LV distribution voltage
80% standard
Nameplate %Z, typically 4–6% (IEC 60076)
For regulation only. ~5 typical for distribution transformers; reactance dominates
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator determines the required transformer size from the connected load, applying the loading rule and calculating key electrical parameters.
Key Formulas
Load kVA = kW ÷ Power Factor
Required kVA = Load kVA ÷ Loading factor
FLC (secondary) = kVA × 1000 ÷ (V × √3)
Fault level = kVA × 100 ÷ (V × √3 × Z%)
Voltage regulation ≈ (%R · cosφ + %X · sinφ) × per-unit loading
The nameplate impedance is split into resistance and reactance using the X/R ratio (%R = %Z ÷ √(1 + (X/R)²), %X = X/R × %R). Distribution transformers are reactance-dominated (X/R ≈ 4–7), so regulation is smallest at unity power factor and rises as the load power factor lags. The figure is a first-order estimate — adjust the X/R ratio to match the manufacturer’s test certificate for a precise value.
Standard Sizes
- Residential: 315-500kVA typical
- Commercial: 500-1000kVA typical
- Industrial: 1000-2500kVA typical
- Impedance: 4-6% standard
Frequently Asked Questions
The 80% loading rule means the transformer is selected so that the expected maximum demand does not exceed 80% of its rated capacity. This provides headroom for: load growth (future additions), diversity variations, transformer losses (which increase with loading), voltage regulation, and cooling capacity. Continuous operation at 100% loading shortens transformer life — the 80% rule ensures a reasonable service life of 20-30 years. For critical loads requiring backup power, see our UPS Sizing Calculator.
Standard distribution transformer ratings (kVA) per IEC 60076 are: 50, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500. For UK DNO substations, common sizes are 315kVA and 500kVA for residential and 800-1000kVA for commercial developments. The primary voltage is typically 11kV or 33kV, with secondary at 400V three-phase.
Impedance voltage (expressed as a percentage, typically 4-6%) represents the voltage needed to circulate full-load current through the transformer with the secondary short-circuited. It affects two things: voltage regulation (higher impedance = more voltage drop under load) and fault level (higher impedance = lower fault current on the secondary). A 5% impedance on a 1000kVA transformer gives approximately 28.9kA fault level on the 400V secondary.
The prospective fault level on the secondary = (kVA × 1000 × 100) / (secondary voltage × √3 × impedance%). For a 500kVA transformer with 5% impedance at 400V: (500000 × 100) / (400 × 1.732 × 5) = 14,434A (14.4kA). All switchgear on the secondary side must have a breaking capacity exceeding this fault level. The actual fault level may be lower if source impedance is significant.
Oil-filled (ONAN/ONAF) transformers are cheaper, more efficient, and better cooled — preferred for outdoor substations. Dry-type (cast resin) transformers are used where fire risk is a concern: inside buildings, car parks, shopping centres, hospitals. Dry-type transformers are typically more expensive (30-50% premium) and physically larger, but they eliminate oil leak and fire risks. For indoor installations in the UK, dry-type is generally required by insurers.
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.