Extension Ventilation Calculator — Part F Requirements

Calculate Part F ventilation requirements for extension rooms including trickle vents, extract rates for wet rooms and purge ventilation specifications.

How We Calculate This

This calculator determines Part F ventilation requirements based on room types and floor area.

Extract rates

Intermittent extract rates per ADF 2021 Vol 1 Table 1.1 (when the room is in use): kitchen 30 l/s with a cooker hood ducted to outside (60 l/s with no hood or a recirculating hood), utility room 30 l/s, bathroom 15 l/s, sanitary accommodation / WC 6 l/s.

Background ventilation

Trickle vents (ADF 2021 Vol 1 Table 1.7): 8,000mm² per habitable room and per kitchen, 4,000mm² for a bathroom, no minimum for a utility room or WC. Divided among windows in each room. Single-storey dwellings use 10,000mm² per habitable room/kitchen, and at least 5 background ventilators are required across the habitable rooms and kitchens (4 for a one-bedroom dwelling) per Table 1.7 Notes.

Purge ventilation

Openable area per ADF 2021 Vol 1 Table 1.4: 1/20 of the room floor area for windows opening 30° or more, sash windows or external doors; 1/10 for hinged or pivot windows opening 15°–30°; windows opening less than 15° are not suitable for purge ventilation.