TradeCalculator.co.uk
Cavity Barrier Calculator
Estimate cavity barrier positions, take-off quantities and product types for fire compartmentation in walls and roofs, with the E30/I15 fire resistance required by Approved Document B.
Used for eaves, compartment-junction and 20m subdivision estimates
Used for party-wall and compartment-junction estimates
Only used when Position = Around Openings
Head + jambs + cill of a typical opening (Around-Openings mode only)
Your cost per linear metre of barrier
Estimate fixings at 600mm centres (typical good practice, not an AD B value)
Safety notice
Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.
Next up: related pages
How We Calculate This
This calculator gives a take-off ESTIMATE of the linear metres of cavity barrier from the barrier position, wall dimensions and opening count, and states the fire resistance that Approved Document B requires. Approved Document B prescribes WHERE cavity barriers go — at edges, junctions and around openings (Volume 1 paragraph 5.18 for houses, 8.3 for flats) — it does not set a linear-metre quantity, so treat the length as an estimate for ordering, not a regulatory minimum.
How it works
- Position: Selects where the cavity barrier is needed — party/compartment wall junctions, around openings, at eaves, or (non-dwellings only) the 20m subdivision of an over-long cavity.
- Material form: Mineral wool (most common), intumescent, timber, steel or composite. AD B paragraph 5.21 lists these forms but notes they do not necessarily achieve the required E30/I15 — the product's tested classification governs.
- Cavity width: The barrier must fill the full cavity width so fire cannot bypass it. Width sizes the product; it does not change the E30/I15 requirement.
- Building height: Over 11m and over 18m, Regulation 7(2) limits the combustibility of external-wall materials.
Fire resistance required (AD B Vol 1)
Tested from each side separately, a cavity barrier must give a minimum of 30 minutes integrity (E30) plus 15 minutes insulation (I15) — paragraph 5.20 (houses) / 8.8 (flats). That is E30 + I15, not 30 minutes of insulation.
Key standards
- AD B Volume 1 (dwellings): Section 5 (houses) / Section 8 (flats) — Cavities and cavity barriers. Section 9 is fire-stopping, which is distinct.
- AD B Volume 2: Section 9, Table 9.1 — the 20m maximum cavity dimension for buildings other than dwellings.
- BS EN 1363-1 / BS EN 13501-2: Fire resistance test and classification (E30 / I15).
- Regulation 7(2): Combustibility limits on external-wall materials at 11m / 18m.
Frequently Asked Questions
In Approved Document B Volume 1 (dwellings) cavity barriers are required to divide cavities and to close their edges, at three locations (paragraph 5.18 for houses, 8.3 for flats): at the edges of cavities, including around openings such as windows, doors and service entry points; at the junction between an external cavity wall and every compartment floor and compartment wall; and at the junction between an internal cavity wall and every compartment floor, compartment wall or other fire-resisting wall or door assembly. Volume 1 does not set a maximum cavity dimension. Note that cavity barriers (Section 5 for houses, Section 8 for flats) are deliberately distinct from fire-stopping, which is Section 9.
The 20m maximum cavity dimension is a Volume 2 rule for buildings other than dwellings (AD B Volume 2, Table 9.1): cavities are limited to 20m, reduced to 10m where exposed cavity surfaces are worse than class C-s3,d2, and there is a 40m limit on the line enclosing a room. It does NOT apply to dwellings. AD B Volume 1 (houses and flats) has no maximum cavity dimension — barriers are required only at edges, junctions and around openings. For a house or flat, you do not subdivide a long cavity at 20m intervals.
AD B Volume 1 paragraph 5.21 lists acceptable forms for a cavity barrier in a stud wall, partition or around an opening: steel at least 0.5mm thick, timber at least 38mm thick, polythene-sleeved mineral wool (or a mineral wool slab) under compression, or a calcium silicate, cement-based or gypsum-based board at least 12mm thick. Crucially the same paragraph notes these forms "do not necessarily achieve" the E30/I15 performance required by paragraph 5.20 — so the tested classification of the specific product governs. A steel or timber window/door frame of the minimum thickness can itself act as the barrier around an opening. Above 18m, materials in the external wall must meet the limited-combustibility requirement of Regulation 7(2).
Tested from each side separately, a cavity barrier should provide a minimum of 30 minutes integrity (E30) AND 15 minutes insulation (I15) — this is AD B Volume 1 paragraph 5.20 for houses and 8.8 for flats. It is E30 plus I15, not 30 minutes of insulation. Performance is demonstrated by test to BS EN 1363-1 and classified to BS EN 13501-2. Proprietary products should carry third-party certification such as BBA or Certifire. For buildings over 18m the external-wall combustibility limits of Regulation 7(2) also apply.
Yes. Cavity barriers must close the edges of cavities, which expressly includes around openings such as windows and doors (AD B Volume 1 paragraph 5.18 for houses, 8.3 for flats), to stop fire spreading unseen within the cavity past the frame. Close the cavity at the head, jambs and cill of each opening; a steel or timber frame of the minimum thickness in paragraph 5.21 can itself form the barrier. This applies to all building heights and is especially important where the cavity contains combustible insulation.
Related Calculators
Was this calculator helpful?
Last updated: June 2026
Verified against UK standards · estimates only, confirm with your supplier.