Fire Compartmentation Calculator — Compartment Sizes per Part B

Determine maximum compartment sizes, fire resistance periods and wall/floor specifications per Approved Document B.

Storeys above ground (single vs multi-storey changes the Table 8.1 area limit)

Floor area of one storey (m²), used to count compartments

Height of the top floor above ground (m) — sets the Table B2 band

Sprinkler system installed (BS EN 12845)

Raises the Table 8.1 compartment limit and can reduce the Table B2 fire-resistance period

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines fire compartmentation requirements based on Approved Document B of the UK Building Regulations. It considers the building purpose group, height, number of storeys and whether sprinklers are installed to calculate maximum compartment sizes and required fire resistance periods.

How it works

  • Purpose group: AD B classifies buildings by use. Each purpose group has its own Table 8.1 compartment-size limits and Table B2 fire-resistance requirements — offices have no area limit, while multi-storey storage buildings are limited by compartment volume rather than floor area.
  • Building height: The height of the top floor sets the Table B2 fire-resistance band (Up to 5 / 11 / 18 / 30m, then more than 30m). It also fixes the Table 8.1 area band at 18m and triggers the mandatory-sprinkler thresholds (flats above 11m; groups 3–7 above 30m).
  • Single vs multi-storey: Table 8.1 area limits differ by storey count — single-storey offices, assembly and industrial buildings are unlimited (single-storey shops are capped at 2000 m² without sprinklers, No limit with), while multi-storey buildings are more tightly capped (e.g. a multi-storey shop is 2000 m², or 4000 m² with sprinklers).
  • Sprinklers: A BS EN 12845 / Appendix E system raises the Table 8.1 area limit and can reduce the Table B2 fire-resistance period.
  • Basements: Fire resistance is set by depth of the lowest basement — up to 10m deep needs 60 minutes (90 for industrial/storage); more than 10m deep needs 90 minutes (120 for industrial/storage).

Key references

  • AD B Vol 2 Appendix B, Table B2: Minimum periods of fire resistance (Table A2 in the 2006/2013 editions; Table B4 in the 2019+2020+2022 edition)
  • AD B Vol 2 Table 8.1: Maximum dimensions of building or compartment
  • AD B Vol 2 §8.11: Provision of compartment walls and floors
  • BS 9999: Code of practice for fire safety in buildings (alternative to AD B)
  • BS EN 12845: Automatic sprinkler systems