Fire Exit Width Calculator

Calculate the minimum fire exit door widths from occupant numbers using Approved Document B Vol 2 Table 2.3 — the banded 750/850/1050mm widths up to 220 persons, then 5mm per person above that. For UK commercial and other non-domestic buildings.

Usable floor area of storey

Leave 0 to auto-calculate from area

Fire exit doors provided

Fire door supply and install

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines minimum fire exit widths using the Approved Document B Vol 2 method (Table 2.3 and Appendix D).

The method

AD B Vol 2 Table 2.3 gives minimum exit widths as fixed bands, not a single linear formula. The 5mm-per-person rule only applies above 220 persons:

  • Occupants = Floor area ÷ floor space factor (Appendix D, Table D1)
  • Up to 60 persons per exit → 750mm clear width
  • Up to 110 persons → 850mm
  • Up to 220 persons → 1050mm
  • More than 220 persons → 5mm per person
  • Widths under 1050mm are not interpolated — snap up to the band (Table 2.3 NOTE 3)
  • Discount the largest exit when 2+ exits are provided; the remaining exits must carry all occupants (paras 2.21–2.22)

Worked example: 84 persons through one remaining exit falls in the “up to 110” band, so the exit is 850mm wide (not 84 × 5mm = 420mm, which NOTE 5 forbids below 220 persons).