Emergency Lighting Layout Calculator
Calculate emergency lighting fitting quantities and spacing per BS 5266 for escape routes, open areas and high-risk zones.
How We Calculate This
This calculator determines the number of emergency lighting fittings and their spacing based on the area type, fitting output and BS 5266-1 lux requirements.
How it works
- Area type: Escape routes need 1 lux, open areas 0.5 lux, high-risk zones 15 lux minimum.
- Fitting output: Higher lumen output allows wider spacing between fittings.
- Spacing formula: Based on lumen output, utilisation factor and required lux level at floor level.
- Key positions: Fittings must be at exits, intersections, direction changes and stairways regardless of spacing.
Frequently Asked Questions
Related Calculators
Fire Door Specification Calculator
Determine FD30/FD60 fire door specification with intumescent strip and hardware.
Fire Stopping Calculator
Calculate fire stopping materials by penetration type and wall/floor fire rating.
Fire Compartmentation Calculator
Calculate fire compartment maximum area and fire wall/door positions by building use.
Fire Escape Distance Calculator
Check maximum travel distances to fire exits by building type.
Emergency Lighting Calculator
Calculate emergency lighting spacing and battery duration per BS 5266.
Last updated: March 2026
All calculations are estimates. Verify with your supplier.
