Determine external wall and cladding fire requirements based on building height AND use, per Approved Document B, Regulation 7(2) and the Building Safety Act 2022. The combustibility rules apply to residential 'relevant buildings' only.
Top floor surface to lowest ground level
Above-ground storeys (reference only — height drives the result)
Total external wall area for reference
Safety notice
Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.
Next up: related pages
How We Calculate This
This calculator determines external wall fire requirements from building height and use, using the rules in Approved Document B and the combustible-materials ban in Regulation 7(2). The height-triggered combustibility rules apply only to residential “relevant buildings” — those containing a dwelling, an institution, or a room for residential purposes, plus hotels, hostels and boarding houses since 1 December 2022.
Residential relevant buildings
- 18m or more: all external-wall materials Class A1 or A2-s1,d0 (non-combustible) — Regulation 7(2), subject only to the limited Reg 7(3) exemptions.
- 11m or more: insulation and filler/core material Class A2-s1,d0 or better — ADB para 10.7 (not B-s3,d2).
- Below 11m: no height-triggered class, but the boundary surface-spread rule still applies.
Offices, assembly and non-residential schools
Regulation 7(2)’s stricter statutory A1/A2-s1,d0 ban and the para 10.7 residential 11m rule do not apply to these uses. However, ADB para 10.6 applies to any building with a storey 18m or more, whatever its use: insulation and filler material must be Class A2-s3,d2 or better. Below 18m, the external wall is assessed via the general ADB external-fire-spread provisions (surface spread near the boundary per Table 10.1, cavity barriers, and material classification or a BS 8414 / BR 135 tested system).
Always applies
- Boundary surface rule: any external surface less than 1000mm from a relevant boundary must be Class B-s3,d2 or better, at any height and any use.
Key standards
- BS EN 13501-1: Reaction to fire classification
- BS 8414 / BR 135: Large-scale external fire spread test
- Regulation 7(2): Combustible-materials ban (residential relevant buildings ≥18m)
- ADB para 10.6: A2-s3,d2 insulation/filler (any building ≥18m)
- ADB para 10.7: A2-s1,d0 insulation/filler (residential ≥11m)
Frequently Asked Questions
The two height-triggered combustibility rules apply to RESIDENTIAL "relevant buildings" only — those containing a dwelling, an institution (hospital, care home, student accommodation) or a room for residential purposes, plus hotels, hostels and boarding houses since 1 December 2022. For these uses: at 18m or more, every material in the external wall (cladding, insulation, filler/core material, spandrel panels) must be non-combustible — Class A1 or A2-s1,d0 — under Regulation 7(2). At 11m or more, any insulation product or filler material must be Class A2-s1,d0 or better under Approved Document B para 10.7. Below 11m there is no height-triggered class, but the boundary surface-spread rule still applies. Offices, assembly/public buildings and non-residential schools are NOT caught by Regulation 7(2) or para 10.7. However, ADB para 10.6 catches ANY building with a storey 18m or more, regardless of use: insulation and filler material must be Class A2-s3,d2 or better. Below 18m, these non-residential uses follow the general ADB external-fire-spread route. These rules were strengthened after the Grenfell Tower fire.
No, PIR (polyisocyanurate) insulation cannot be used in the external walls of residential relevant buildings 18m or more in height. PIR foam typically achieves Euroclass B (occasionally C), which does not meet the A1 or A2-s1,d0 requirement of Regulation 7(2). The only common insulation materials that achieve Class A1 or A2-s1,d0 are mineral wool (stone wool and glass wool), cellular glass and some calcium silicate products. This restriction applies to all materials within the external wall, not just the visible cladding. The same A2-s1,d0 limit applies to insulation and filler material at 11m and above in residential buildings (ADB para 10.7), so PIR is also not acceptable there.
BS 8414 is a large-scale fire test for external cladding systems. A full-size cladding system is built and subjected to a severe fire from a combustion chamber at the base. The test measures fire spread up the facade, internal temperatures within the cladding system and any falling debris. Results are assessed against BR 135 criteria. A BS 8414 / BR 135 tested system is a recognised route to demonstrate the general ADB external-fire-spread requirements. However, for a residential relevant building it cannot override the prescriptive material rules: the Regulation 7(2) A1/A2-s1,d0 ban at 18m and the ADB para 10.7 A2-s1,d0 insulation/filler requirement at 11m apply in their own right to the regulated components. BS 8414 evidence remains useful for components not caught by those prescriptive rules and for non-residential buildings following the general external-fire-spread route.
Building height is measured from the ground level on the lowest side of the building to the top of the floor surface of the topmost storey. It does not include the roof unless the roof space is a usable storey. For buildings on sloping ground, the measurement is taken from the lowest adjacent ground level. This is the definition used in Regulation 7 and Approved Document B. A building with its top floor at 18.0m is subject to the full non-combustible requirements.
The Building Safety Act 2022 and associated regulations have introduced requirements for existing buildings over 11m with specific cladding types to be remediated. Building owners of high-rise residential buildings (over 18m) with unsafe cladding must carry out remediation. The act established the Building Safety Regulator and requires building safety cases for high-rise residential buildings. Government funding schemes are available for leaseholders in buildings over 11m with unsafe cladding.