Commercial Fire Strategy Calculator

Determine fire strategy requirements for commercial buildings including travel distances, exit widths, fire resistance and compartmentation per Approved Document B.

Total usable floor area per storey

Floor space factor per AD B Appendix D Table D1 (office 6, shop sales 2, assembly hall 0.5, storage 30)

Actual number of exits in your design

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines the key fire strategy parameters for commercial buildings based on building use, size, height and installed fire protection systems. It follows Approved Document B and BS 9999 guidance.

How it works

  • Purpose group: Sets the floor space factor (Table D1), travel distances (Table 2.1) and compartment size limits (Table 8.1).
  • Occupancy: Floor area divided by the floor space factor gives the design occupancy used for exit sizing.
  • Exit width: Banded per Table 2.3 — 750mm up to 60 people, 850mm up to 110, 1050mm up to 220, then 5mm per person above 220 (the 5mm rule does not apply below 220).
  • Number of exits: Table 2.2 — 1 up to 60 people, 2 up to 600, 3 above 600; larger occupancies are governed by exit-width discounting, not a higher count.
  • Fire resistance: Appendix B Table B2, by purpose group and height of the top floor above ground.
  • Sprinkler trade-off: Does not extend AD B travel distances; it can enlarge compartment areas (Table 8.1) and lower fire-resistance periods (Table B2 sprinklered column). Longer travel needs a BS 9999 risk-profile assessment.