Window Fire Escape Calculator

Check whether windows meet Approved Document B fire escape requirements for clear opening dimensions, sill height and egress compliance in UK dwellings.

Width when fully open (min 450mm)

Height when fully open (min 450mm)

Max 1100mm (AD B); no lower Part B limit

If replacing non-compliant windows

How We Calculate This

This calculator checks whether a window meets the fire escape (egress) requirements of Approved Document B of UK Building Regulations.

Window opening requirements (AD B Vol 1, para 2.10)

Clear opening ≥ 0.33 m², minimum 450mm in any direction

  • Minimum clear width: 450mm
  • Minimum clear height: 450mm
  • Minimum clear area: 0.33 m²
  • Bottom of openable area: max 1100mm above floor level (no lower Part B limit)
  • Restrictors must be easily overridable without tools

Where a window counts as escape (paras 2.1–2.6)

  • Ground & upper storeys up to 4.5m above ground: a compliant escape window (or external door) is an acceptable means of escape.
  • Floor more than 4.5m above ground: a window is not sufficient on its own — a protected stairway (REI 30) to a final exit, or an alternative escape route, is required.
  • Floor more than 7.5m above ground: an alternative escape route must be provided.

The floor height used for the 4.5m/7.5m test is estimated at about 2.7m per storey; measure the actual floor-to-ground height where it is close to 4.5m. AD B does not rely on fire-service ladder rescue for dwellings.