Commercial Ventilation Calculator — Fresh Air Rates

Calculate the minimum fresh-air ventilation rate for offices, shops, restaurants, gyms, and other commercial spaces. Uses the Approved Document F Volume 2 (2021) whole-building rule — the greater of the per-person and per-m² rate.

Internal floor area of the space

Expected occupancy (0 = use typical density)

Typical commercial: 2.7-3.5m

How We Calculate This

This calculator returns the minimum fresh-air ventilation rate for a commercial space using the Approved Document F Volume 2 (2021) whole-building rule for buildings other than dwellings: take the greater of a per-person rate and a per-m² floor-area rate. For offices this is the greater of 10 l/s per person or 1 l/s per m².

Design method

Minimum ventilation = MAX(Per-person rate × Occupancy, Per-m² rate × Floor area)

The person-based rate accounts for CO2 and body odour generated by occupants. The area-based rate accounts for emissions from the building fabric and furnishings. Approved Document F Volume 2 takes the higher of the two as the regulatory minimum.

This is a minimum, not a full design rate

The current European design standard, BS EN 16798-1:2019, adds the occupant and building components rather than taking the higher of the two (qtot = n·qp + A·qB; Category II low-polluting building = 7 l/s/person + 0.7 l/s/m²). A full EN 16798-1 design therefore gives a higher rate than the Approved Document F minimum returned here — use this tool as a compliance floor, then size the system to the design standard for the chosen indoor-air-quality category.

Occupancy densities

Where the actual occupancy is not known, indicative typical design densities are used, ranging from about 0.04 persons/m² for hotel bedrooms to 0.8 persons/m² for lecture halls. These are design conventions rather than figures from a single standard — the calculator lets you override the headcount or density for a specific project.

Duct sizing

The main supply duct diameter is calculated from the total ventilation rate and a design velocity (default 5 m/s for commercial systems, per CIBSE Guide B2 low-pressure ductwork practice) using continuity, Q = V × A. Lower velocities reduce noise but require larger ducts.

Frequently Asked Questions

Was this calculator helpful?