MVHR Unit Sizing Calculator — Balanced Ventilation

Size MVHR units by calculating total extract rates from wet rooms and matching supply to habitable rooms per Approved Document F (2021) Table 1.3.

8 L/s extract each

6 L/s extract each

13 L/s MVHR extract each (ADF Table 1.2)

How We Calculate This

This calculator sizes MVHR units (System 4 per Approved Document F) by balancing the extract demand from wet rooms against the supply to habitable rooms.

Sizing methodology

  • Sum continuous extract rates from all wet rooms — kitchen 13, bathroom/utility 8, WC 6 L/s (ADF 2021 Table 1.2). Every wet room keeps its own terminal even if a cooker hood is fitted (para 1.70)
  • Calculate whole-dwelling rate (ADF 2021 Table 1.3, and the 0.3 L/s per m² floor-area check — take the greater)
  • Unit capacity = max(total extract, whole dwelling rate)
  • Boost mode = trickle rate × boost factor (1.5× is a design rule of thumb, not an ADF requirement; the true regulatory boost is every wet room at its Table 1.2 high rate at once — follow the unit’s commissioning data)
  • Supply air should be distributed proportionately to each habitable room’s volume (ADF 2021 para 1.67); the breakdown shows an indicative equal split only, to be re-apportioned and balanced at commissioning

ADF 2021 Table 1.3 — whole-dwelling rates

  • 1 bedroom: 19 L/s
  • 2 bedrooms: 25 L/s
  • 3 bedrooms: 31 L/s
  • 4 bedrooms: 37 L/s
  • 5 bedrooms: 43 L/s (add 6 L/s per further bedroom)

Once a unit is shortlisted, check its specific fan power against the Part L limit for balanced MVHR with our fan SFP calculator.