TradeCalculator.co.uk
Airtightness Estimator — Air Permeability at 50 Pa
Indicative pre-test estimate of building airtightness from leakage paths. Air permeability in m³/h.m² at 50Pa against the Part L limit (8) and the notional good-practice target (5). Only a blower-door test to BS EN ISO 9972 confirms compliance.
Total external surface area
~1.5 m³/h each (indicative)
~3.0 m³/h each (indicative)
~4.0 m³/h each (indicative)
Gas, water, electric entries (~2.0 m³/h each)
~0.5 m³/h each if sealed/capped; unsealed downlights leak far more (~20 m³/h measured)
~2.5 m³/h each (indicative)
Background leakage through fabric
Your design target
Next up: related pages
How We Calculate This
This estimator gives an indicative pre-test figure by summing leakage contributions from individual building penetrations and the general fabric leakage rate. The result is dominated by the base fabric leakage rate you assume; the penetration allowances below are rough rules of thumb, not measured values. Only a blower-door test to BS EN ISO 9972 (ATTMA TSL1) gives a figure you can use for Part L compliance.
The formula
Penetration leakage = Σ(Item count × Leakage rate per item)
Fabric leakage = Envelope area × Base leakage rate
Air permeability = Total leakage ÷ Envelope area
For example, a house with 250 m² envelope, 10 windows (15 m³/h), 3 doors (9 m³/h), 20 spotlights (10 m³/h), and 3.0 base rate: Fabric = 250 × 3.0 = 750. Total = 750 + 34 = 784 m³/h. Permeability = 784 ÷ 250 = 3.14 m³/h.m².
Indicative leakage allowances (rule of thumb)
These are rough allowances for a quick estimate, not standardised values. Real component leakage varies widely with detailing and sealing — follow component datasheets and the blower-door test result for anything you rely on.
- Window: ~1.5 m³/h per window at 50 Pa
- External door: ~3.0 m³/h per door
- Loft hatch: ~4.0 m³/h per hatch (uninsulated/unsealed hatches leak much more)
- Recessed spotlight: ~0.5 m³/h per light if sealed or fitted with an airtight cover — an unsealed downlight can measure around 20 m³/h @50Pa (Thermahood / Build Test Solutions field data), so cap them
- Extract fan: ~2.5 m³/h per fan
Frequently Asked Questions
Part L 2021 (Conservation of Fuel and Power, Volume 1: Dwellings) sets a limiting (backstop) air permeability of 8 m³/h.m² at 50 Pa for new dwellings — the absolute maximum permitted. The notional dwelling used for the energy-performance check is specified at 5 m³/h.m², so designing to 5 is the good-practice target that eases overall compliance, not a separate legal limit. The Future Homes Standard was published on 24 March 2026 and comes into force on 24 March 2027 (with a 12-month transition). It keeps the 8 m³/h.m² legal backstop but tightens the notional dwelling to 3 m³/h.m² at 50 Pa, with the notional specifying mechanical extract ventilation (dMEV; many builders fit MVHR instead). Passivhaus requires 0.6 air changes per hour at 50 Pa, roughly 1-2 m³/h.m². Most new builds achieve 3-5 m³/h.m² with good practice.
The biggest leakage paths are: service penetrations (pipes, cables entering the building), window and door junctions, loft hatches, letterboxes, and recessed spotlights. In older buildings, suspended timber floors and party walls are also major sources. Sealing these penetrations with appropriate tapes, membranes, and grommets is the most cost-effective way to improve airtightness.
A blower door test (BS EN ISO 9972, with UK testing to ATTMA TSL1) uses a calibrated fan installed in an external doorway to pressurise or depressurise the building to 50 Pa. The fan speed needed to maintain this pressure difference tells you the total air leakage rate, expressed as m³/h.m² of envelope area. Costs are market-variable: a single new-build dwelling test typically starts from around £95 plus VAT, with more for larger or complex dwellings and volume discounts on multi-plot developments — treat any figure as indicative and get a quote. Since June 2022 every new-build plot in England needs its own air test.
Yes — without adequate ventilation, an airtight building can suffer from poor indoor air quality, condensation, and mould. Buildings achieving below 5 m³/h.m² should have mechanical ventilation with heat recovery (MVHR). Below 3 m³/h.m², MVHR is essential. The principle is 'build tight, ventilate right' — control air movement rather than relying on unplanned draughts.
Air permeability (q50, m³/h.m²) measures leakage per unit of building envelope area — used in UK Building Regulations. Air changes per hour at 50 Pa (n50) measures how many times the building's internal volume is replaced per hour — used in Passivhaus. To convert: n50 = (Air permeability × Envelope area) ÷ Building volume. For a typical dwelling the envelope area and internal volume are numerically similar, so q50 and n50 come out roughly EQUAL (ratio ≈ 1) — the difference grows only for very small or very large/unusual building forms. Do not confuse this with the everyday natural air-change rate: SAP uses the 'divide by 20' rule of thumb (background infiltration ≈ q50 ÷ 20) to estimate the air-change rate under normal pressures rather than the 50 Pa test pressure.
Related Calculators
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.