Background Ventilation Calculator — Part F Trickle Vents
Calculate minimum whole dwelling ventilation rate, trickle ventilator equivalent areas per room, and purge ventilation openings per Approved Document F Table 5.1a and 5.2a.
Determines whole dwelling vent rate
5000 mm² EA each
5000 mm² EA each
2500 mm² EA each
2500 mm² EA each
2500 mm² EA each
How We Calculate This
This calculator determines background ventilation requirements per Approved Document F (2021) System 1 (background ventilators with intermittent extract).
ADF Table 5.1a — whole dwelling rates
- 1 bedroom: 14 L/s
- 2 bedrooms: 21 L/s
- 3 bedrooms: 28 L/s
- 4 bedrooms: 35 L/s
- 5 bedrooms: 42 L/s
- Or 0.3 L/s per m² floor area (whichever is greater)
ADF Table 5.2a — trickle vent EA
- Habitable rooms (bedrooms, living): 5000 mm² EA each
- Wet rooms (kitchen, bathroom, WC): 2500 mm² EA each