Ventilation Commissioning Calculator — Flow Balance Check

Check ventilation system commissioning by comparing target vs measured flow rates at each terminal. Verify system balance within the required tolerance per ADF.

Or leave blank and enter total below

Divided equally if per-terminal not set

Enter one value per terminal, separated by commas

How We Calculate This

This calculator compares target design flow rates against measured flow rates for each ventilation terminal to assess system balance and compliance.

Commissioning check

  • Enter the target flow rate per terminal (or total divided equally)
  • Enter measured flows as comma-separated values
  • Each terminal is checked against the ±10% tolerance
  • Overall system balance is verified

Pass/fail criteria

Each terminal must be within ±10% of its design flow rate (ADF and BSRIA AG3). The total system flow must also be within ±10% of the total design flow. Any terminal outside tolerance requires damper adjustment and re-measurement.