Ventilation Commissioning Calculator — Flow Balance Check

Check ventilation system commissioning by comparing target vs measured flow rates at each terminal. Flags terminals below design (the Approved Document F pass test) and applies the BSRIA BG 49 ±10% air-balance tolerance.

Or leave blank and enter total below

Divided equally if per-terminal not set

Enter one value per terminal, separated by commas

How We Calculate This

This calculator compares target design flow rates against measured flow rates for each ventilation terminal to assess system balance and compliance.

Commissioning check

  • Enter the target flow rate per terminal (or total divided equally)
  • Enter measured flows as comma-separated values
  • Each terminal is checked against the BSRIA BG 49 ±10% balance tolerance
  • Any terminal reading below 100% of design is flagged separately, because the Approved Document F pass test is measured ≥ design
  • Overall system balance is verified

Pass/fail criteria

The Building Regulations pass criterion for new dwellings is set by Approved Document F Volume 1 (2021), Appendix C: the measured air flow at each fan/terminal must be equal to or greater than the design value. A terminal below design is not compliant and must be adjusted until it matches design — there is no negative allowance in ADF.

The familiar ±10% air-balance band comes from BSRIA BG 49 (Commissioning Air Systems), a best-practice tolerance for balancing, not a Building Regulations requirement. This tool reports both: terminals within ±10% (the BG 49 balance check) and terminals below design (the ADF compliance flag). The flow-measuring instrument must itself have ±5% accuracy and be UKAS-calibrated within 12 months (ADF Vol 1, Section 4).