Calculate insulation thickness between and over rafters to achieve Part L U-value of 0.15 W/m²K using PIR, mineral wool or phenolic board.

Total sloping ceiling area to insulate

Depth of existing rafters

AD L Vol 1 2021 (inc. 2023 amendments) Table 4.2: 0.15 W/m²K for a new sloping ceiling in an existing dwelling

Material cost per m²

How We Calculate This

This calculator gives an indicative insulation thickness to achieve the target U-value, based on the declared thermal conductivity (λ) of the chosen insulation.

The formula (single-layer estimate)

Thickness (mm) = (λ / Target U-value) × 1000

Between rafters = min(Rafter Depth, Total Thickness)

Over rafters = Total Thickness − Between Rafters

This is a quick rule-of-thumb that treats the build-up as one homogeneous layer of insulation. It ignores the internal/external surface resistances (roof Rsi ≈ 0.10, Rso ≈ 0.04 m²K/W), the plasterboard and vapour control layer, any ventilation gap, and — most importantly — thermal bridging through the timber rafters, which carry roughly 12–15% of a between-rafter area at λ ≈ 0.13 W/mK and raise the effective U-value. The actual U-value must be confirmed by a full BR 443 calculation (the method Approved Document L requires), and in practice you will usually need a layer thicker than the bare λ/U figure once bridging is accounted for. Always follow the manufacturer's certified system build-up and confirm with Building Control.

Insulation types (for U=0.15, single-layer estimate)

  • Phenolic board (Kingspan K107): λ 0.019 — ≈127mm
  • PIR board (Celotex/Kingspan): λ 0.022 — ≈147mm
  • Mineral wool: λ 0.035 — ≈233mm