TradeCalculator.co.uk
Loft Electrical Calculator — Circuits, Cable Routes & Consumer Unit
Calculate electrical requirements for a loft conversion: lighting circuits, ring finals, shower circuits, consumer unit spare ways and cable routes.
Ceiling lights, wall lights, switches
13A double socket outlets
Dedicated circuit for electric shower
Interlinked mains + battery (BS 5839-6 Grade D1, LD2)
Average installed cost per point
Average cable length per point
Extra spare ways for future use
Next up: related pages
How We Calculate This
This calculator estimates the electrical circuits and components needed for a loft conversion. The divisors below are trade design conventions, not fixed BS 7671 limits — verify the final design against the regulations and the consumer-unit layout.
Circuit count (design conventions)
Lighting Circuits = ceil(Light Points ÷ 12) — based on the ~100W/point lighting demand convention (IET On-Site Guide), giving about 12 points on a 6A circuit at 230V with diversity.
Ring Finals = ceil(Sockets ÷ 10) — a practical loft-room rule of thumb. The actual BS 7671 limit on a 32A ring final is ≤100m² floor area (outlets effectively unlimited within that area), not a socket count.
CU Ways = Total Circuits + Spare Ways
Typical circuits
- Lighting: 6A MCB, 1.0mm² T&E cable
- Ring final: 32A MCB, 2.5mm² T&E cable
- Shower: MCB sized from the design current Ib = kW×1000÷230V, choosing the smallest standard rating with In ≥ Ib — 40A up to 9kW, 45A for 9.5–10kW, 50A for 10.5–12kW (10.5kW = 45.7A already exceeds a 45A breaker); 10mm² T&E cable (16mm² where enclosed in loft insulation, which derates the cable under reference Methods 100–103)
- RCD protection: 30mA on every new socket-outlet circuit (BS 7671:2018+A4:2026 Reg 411.3.3) and lighting circuit (Reg 411.3.4) — dual-RCD or all-RCBO board; Type A device for the shower
- Smoke detection: BS 5839-6 Grade D1, Category LD2 — interlinked mains + battery alarms on every storey of the escape route plus the principal habitable room; heat alarm in any kitchen
Loft-conversion electrical work is notifiable under Approved Document P — use a registered competent person or notify building control.
Frequently Asked Questions
Yes. Electrical work in a loft conversion is notifiable under Part P because it involves new circuits in a new habitable space. The work must be done by a registered competent person (e.g. NICEIC or NAPIT) who can self-certify, or be notified to building control and inspected. An Electrical Installation Certificate plus a Building Regulations compliance certificate is issued on completion.
Typically: 1 lighting circuit (6A MCB — about 12 points at the ~100W/point demand convention), 1 ring final circuit for sockets (32A MCB, limited by ≤100m² floor area not socket count per BS 7671), and optionally a dedicated shower circuit. The shower MCB follows the design current Ib = kW×1000÷230V, choosing the smallest standard MCB with In ≥ Ib: an 8.5kW shower draws ~37A (40A MCB), 9.5–10kW draws 41–43.5A (45A MCB), and 10.5–12kW draws 45.7–52.2A (50A MCB, because 10.5kW = 45.7A exceeds a 45A breaker). A smoke detector circuit is also needed if not already interconnected with the existing system.
Yes. Under the 18th Edition Wiring Regulations (BS 7671:2018+A4:2026, the current Orange Book) every new domestic socket-outlet circuit must have additional protection by a 30mA RCD under Reg 411.3.3, and every lighting circuit under Reg 411.3.4 — so the new loft circuits need a dual-RCD or all-RCBO consumer unit. An electric shower in a bathroom requires a Type A RCD/RCBO. If your existing board has no spare ways or is an old rewireable fuse board, it will likely need upgrading.
Possibly. You need spare ways in the consumer unit for the new circuits (typically 2-4 ways). If your existing CU has no spare ways or is an old-style rewireable fuse board, it will need upgrading to a board that gives 30mA RCD protection to all the new final circuits (dual-RCD or all-RCBO) to comply with the 18th Edition Wiring Regulations (BS 7671:2018+A4:2026).
A loft conversion is designed to BS 5839-6 Grade D1, Category LD2 (referenced by Approved Document B): interlinked, mains-wired alarms with battery backup, fitted on every storey along the escape route plus the principal habitable room, with a HEAT alarm (not smoke) in any kitchen. For a typical two-storey house becoming three storeys that means at least an alarm in the new loft room and on each landing below, all interlinked so they sound together.
Cables typically run from the consumer unit (usually ground floor) up through the existing ceiling void, through the floor structure to the loft. Cables in walls must be in safe zones (vertical or horizontal from accessories) or protected in conduit. Cable routes through fire barriers need fire-stopping.
Related Calculators
Was this calculator helpful?
Last updated: May 2026
Verified against UK standards · estimates only, confirm with your supplier.