Skip to content

Loft Electrical Calculator — Circuits, Cable Routes & Consumer Unit

Calculate electrical requirements for a loft conversion: lighting circuits, ring finals, shower circuits, consumer unit spare ways and cable routes.

Ceiling lights, wall lights, switches

13A double socket outlets

Shower Circuit

Dedicated circuit for electric shower

Smoke Detectors

Interlinked mains + battery (BS 5839-6 Grade D1, LD2)

Average installed cost per point

How We Calculate This

This calculator estimates the electrical circuits and components needed for a loft conversion. The divisors below are trade design conventions, not fixed BS 7671 limits — verify the final design against the regulations and the consumer-unit layout.

Circuit count (design conventions)

Lighting Circuits = ceil(Light Points ÷ 12) — based on the ~100W/point lighting demand convention (IET On-Site Guide), giving about 12 points on a 6A circuit at 230V with diversity.

Ring Finals = ceil(Sockets ÷ 10) — a practical loft-room rule of thumb. The actual BS 7671 limit on a 32A ring final is ≤100m² floor area (outlets effectively unlimited within that area), not a socket count.

CU Ways = Total Circuits + Spare Ways

Typical circuits

  • Lighting: 6A MCB, 1.0mm² T&E cable
  • Ring final: 32A MCB, 2.5mm² T&E cable
  • Shower: MCB sized from the design current Ib = kW×1000÷230V, choosing the smallest standard rating with In ≥ Ib — 40A up to 9kW, 45A for 9.5–10kW, 50A for 10.5–12kW (10.5kW = 45.7A already exceeds a 45A breaker); 10mm² T&E cable (16mm² where enclosed in loft insulation, which derates the cable under reference Methods 100–103)
  • RCD protection: 30mA on every new socket-outlet circuit (BS 7671:2018+A4:2026 Reg 411.3.3) and lighting circuit (Reg 411.3.4) — dual-RCD or all-RCBO board; Type A device for the shower
  • Smoke detection: BS 5839-6 Grade D1, Category LD2 — interlinked mains + battery alarms on every storey of the escape route plus the principal habitable room; heat alarm in any kitchen

Loft-conversion electrical work is notifiable under Approved Document P — use a registered competent person or notify building control.

Frequently Asked Questions

Was this calculator helpful?

Last updated: May 2026

Verified against UK standards · estimates only, confirm with your supplier.