TradeCalculator.co.uk
Part L Air Permeability & Airtightness
Air permeability targets, testing requirements, common leakage paths, and implications for ventilation strategy, referencing Approved Document L: Conservation of Fuel and Power, Volume 1 - Dwellings (2021 edition, effective 15 June 2022).
Air Permeability Targets (AD-L 2021)
| Parameter | Value | Notes |
|---|---|---|
| Maximum design air permeability | 8 m³/(h.m²) at 50 Pa | Backstop — must not exceed this |
| Notional dwelling value | 5 m³/(h.m²) at 50 Pa | Used in SAP notional dwelling |
| Good practice target | 3-5 m³/(h.m²) at 50 Pa | Achievable with careful detailing |
| Passivhaus standard | ≤ 0.6 ACH at 50 Pa | Approximately 1-2 m³/(h.m²) |
| MVHR threshold | ≤ 3 m³/(h.m²) at 50 Pa | Below this, MVHR is typically required |
Ventilation Strategy by Airtightness (AD-F & AD-L)
| Air Permeability Range | Suitable Ventilation Systems |
|---|---|
| > 5 m³/(h.m²) | System 1 (intermittent + trickle vents) or System 2 (PSV) |
| 3-5 m³/(h.m²) | System 3 (continuous MEV) or System 4 (MVHR) |
| < 3 m³/(h.m²) | System 4 (MVHR) required |
Common Air Leakage Paths and Sealing Methods
| Leakage Path | Typical Contribution (%) | Sealing Method |
|---|---|---|
| Window/door frames | 15-25 | Expanding foam, tape, or sealant between frame and wall |
| Wall/floor junctions | 10-20 | Flexible sealant or membrane at junction |
| Wall/ceiling junctions | 10-15 | Continuous plaster bead or sealant |
| Service penetrations (pipes, cables) | 10-20 | Intumescent sealant, grommets, or fire-rated foam |
| Loft hatch | 5-10 | Draught-sealed, insulated hatch with compression seal |
| Recessed downlights | 5-15 | Airtight rated fittings or airtight covers above |
| Party wall zone | 5-15 | Sealed cavity at eaves level, continuous plaster |
Testing Requirements
| Requirement | Detail |
|---|---|
| Test standard | BS EN ISO 9972 (Method 1 — building in use) |
| Mandatory for | All new dwellings |
| Tester accreditation | UKAS or ATTMA registered |
| Test pressure | 50 Pa (both pressurisation and depressurisation) |
| Result unit | m³/(h.m²) of envelope area at 50 Pa |
Scotland & Northern Ireland
Scotland has its own airtightness requirements under Technical Handbook Section 6 (Energy), with a maximum air permeability of 10 m³/(h.m²) at 50 Pa for dwellings. Northern Ireland follows Technical Booklet F2. Wales follows its own edition of AD-L with similar targets to England. Testing requirements vary by jurisdiction.
Related Calculators
Use the U-Value Calculator for thermal performance, or the Part F Ventilation Rates for ventilation strategy guidance.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Frequently Asked Questions
Related Calculators
Part L U-Value Targets History
Part L U-value requirements from 2006 to 2021: walls, floors, roofs, windows and doors targets by edition year.
Part O Overheating Limits
AD-O overheating: glazing area limits by orientation, cross-ventilation requirements, shading factors, and TM59 criteria.
Insulation U-Values
Part L target U-values for walls, floors, roofs and windows with insulation thicknesses to achieve compliance.
Part L 2021 U-Value Targets
Part L 2021 target U-values for all building elements with notional dwelling values.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.