Building Regulations U-Values for Walls, Roofs and Floors (Part L 2021)

The current UK building regulations U-value targets for walls, roofs, floors, windows and doors: new dwellings, extensions and existing buildings in England under Approved Document L 2021.

UK building regulations set a maximum U-value for every part of a building’s fabric: walls, roofs, floors, windows and doors. In England these limits come from Approved Document L (Part L), 2021 edition incorporating 2023 amendments, and the tables below are the values currently in force. For how these figures have changed since 2006, see the Part L U-value history; for the thermal conductivity of specific insulation materials rather than the regulatory targets, see the insulation U-values reference.

New-Build Dwellings (Part L Vol 1, 2021)

New-Build Dwellings (Part L Vol 1, 2021)
ElementNotional Target (W/m²K)Limiting Value (W/m²K)
External wall0.180.26
Party wall (between dwellings)0.000.20
Floor (ground floor)0.130.18
Pitched roof (insulation at ceiling)0.110.16
Pitched roof (insulation at rafter)0.110.16
Flat roof0.110.16
Windows1.21.6
Roof windows1.21.6
External doors (opaque)1.01.6
Glazed doors (>60% glazed)1.21.6

Extensions to Existing Dwellings

Extensions to Existing Dwellings
ElementTarget U-value (W/m²K)
External wall0.18
Floor0.18
Roof (all types, pitched or flat)0.15
Windows, roof windows, glazed doors1.4 (or WER Band B)
Rooflights2.2
Opaque doors1.4

Renovation of Existing Elements

Renovation of Existing Elements
ElementThreshold (W/m²K)Improved target (W/m²K)
Roof (all types)0.350.16
Wall (cavity insulation, where suitable)0.700.55
Wall (internal or external insulation)0.700.30
Floor0.700.25

Table 4.3 applies to renovating or retaining existing thermal elements. Retained elements worse than the threshold should be upgraded to the improved value where technically feasible with a simple payback of 15 years or less. Table 4.3 contains no windows or doors rows: replacement windows and doors are new elements and must meet Table 4.2 (1.4 W/m²K).

Source: Approved Document L, Volume 1: Dwellings, 2021 edition incorporating 2023 amendments (Tables 1.1, 4.1, 4.2 and 4.3), in force in England. Figures re-verified against the gov.uk PDF, July 2026.

Correction

July 2026: U-values on this page were re-verified against the Approved Document L Volume 1 "2021 edition incorporating 2023 amendments" PDF on gov.uk. Corrections: the new-build flat roof limiting value was corrected from 0.18 to 0.16 W/m²K (Table 4.1 sets a single value for all roof types) and the party wall limiting value of 0.20 was added; the extension roof values were corrected from 0.16 to 0.15 W/m²K (Table 4.2); the renovation table now follows Table 4.3 as printed, with a single roof row (threshold 0.35, improved 0.16) replacing the previous 0.16 and 0.18 pitched and flat split, and the windows and doors row removed because Table 4.3 contains no window or door entries. Replacement windows and doors fall under Table 4.2 at 1.4 W/m²K.