Building Regulations U-Values for Walls, Roofs and Floors (Part L 2021)
The current UK building regulations U-value targets for walls, roofs, floors, windows and doors: new dwellings, extensions and existing buildings in England under Approved Document L 2021.
UK building regulations set a maximum U-value for every part of a building’s fabric: walls, roofs, floors, windows and doors. In England these limits come from Approved Document L (Part L), 2021 edition incorporating 2023 amendments, and the tables below are the values currently in force. For how these figures have changed since 2006, see the Part L U-value history; for the thermal conductivity of specific insulation materials rather than the regulatory targets, see the insulation U-values reference.
New-Build Dwellings (Part L Vol 1, 2021)
| Element | Notional Target (W/m²K) | Limiting Value (W/m²K) |
|---|---|---|
| External wall | 0.18 | 0.26 |
| Party wall (between dwellings) | 0.00 | 0.20 |
| Floor (ground floor) | 0.13 | 0.18 |
| Pitched roof (insulation at ceiling) | 0.11 | 0.16 |
| Pitched roof (insulation at rafter) | 0.11 | 0.16 |
| Flat roof | 0.11 | 0.16 |
| Windows | 1.2 | 1.6 |
| Roof windows | 1.2 | 1.6 |
| External doors (opaque) | 1.0 | 1.6 |
| Glazed doors (>60% glazed) | 1.2 | 1.6 |
Extensions to Existing Dwellings
| Element | Target U-value (W/m²K) |
|---|---|
| External wall | 0.18 |
| Floor | 0.18 |
| Roof (all types, pitched or flat) | 0.15 |
| Windows, roof windows, glazed doors | 1.4 (or WER Band B) |
| Rooflights | 2.2 |
| Opaque doors | 1.4 |
Renovation of Existing Elements
| Element | Threshold (W/m²K) | Improved target (W/m²K) |
|---|---|---|
| Roof (all types) | 0.35 | 0.16 |
| Wall (cavity insulation, where suitable) | 0.70 | 0.55 |
| Wall (internal or external insulation) | 0.70 | 0.30 |
| Floor | 0.70 | 0.25 |
Table 4.3 applies to renovating or retaining existing thermal elements. Retained elements worse than the threshold should be upgraded to the improved value where technically feasible with a simple payback of 15 years or less. Table 4.3 contains no windows or doors rows: replacement windows and doors are new elements and must meet Table 4.2 (1.4 W/m²K).
Source: Approved Document L, Volume 1: Dwellings, 2021 edition incorporating 2023 amendments (Tables 1.1, 4.1, 4.2 and 4.3), in force in England. Figures re-verified against the gov.uk PDF, July 2026.
Correction
July 2026: U-values on this page were re-verified against the Approved Document L Volume 1 "2021 edition incorporating 2023 amendments" PDF on gov.uk. Corrections: the new-build flat roof limiting value was corrected from 0.18 to 0.16 W/m²K (Table 4.1 sets a single value for all roof types) and the party wall limiting value of 0.20 was added; the extension roof values were corrected from 0.16 to 0.15 W/m²K (Table 4.2); the renovation table now follows Table 4.3 as printed, with a single roof row (threshold 0.35, improved 0.16) replacing the previous 0.16 and 0.18 pitched and flat split, and the windows and doors row removed because Table 4.3 contains no window or door entries. Replacement windows and doors fall under Table 4.2 at 1.4 W/m²K.
Related Calculators & Reference
Use the U-Value Calculator to check your construction meets these targets, or the Insulation Thickness Calculator to find the required insulation depth. See also the Part L U-value history (2006-2021), the insulation U-values reference, the SAP glossary entry and Thermal Bridge glossary entry.
Next up: related pages
Frequently Asked Questions
For a new-build dwelling in England, Approved Document L 2021 sets a limiting (backstop) U-value of 0.26 W/m²K for external walls and 0.16 W/m²K for roofs, with tighter notional design values of 0.18 W/m²K (wall) and 0.11 W/m²K (roof) used in the SAP calculation. For an extension, new walls and roofs must meet Table 4.2: 0.18 W/m²K (wall) and 0.15 W/m²K (roof). Renovating a retained wall or roof uses Table 4.3: wall 0.55 W/m²K by cavity fill or 0.30 W/m²K by internal or external insulation, roof 0.16 W/m²K. See the full tables below for floors, windows and doors.
Target U-values (also called notional dwelling values) are the values used in the notional dwelling SAP calculation and represent the expected performance level. Limiting U-values are the absolute worst-case values that individual elements must not exceed, regardless of how well other elements perform. You cannot compensate for a poor wall U-value by having better windows, for example - every element must at least meet the limiting value.
Yes, but they are different rather than simply looser. New elements in an extension must meet AD L 2021 (as amended) Table 4.2: walls 0.18 W/m²K, floors 0.18, roofs 0.15 (a single value covering pitched and flat), windows 1.4 (or Window Energy Rating Band B), doors 1.4 and rooflights 2.2. The wall, floor and roof limits are stricter than the new-build limiting values because an extension has no whole-dwelling SAP trade-off. Upgrading a retained existing element uses Table 4.3: wall 0.55 by cavity fill or 0.30 by internal or external insulation, floor 0.25, roof 0.16. Table 4.3 has no windows row: replacement windows fall under Table 4.2 at 1.4 W/m²K.
Part L 2021 tightened U-value targets compared to Part L 2013. Key changes: wall limiting dropped from 0.30 to 0.26 W/m²K, pitched roof limiting from 0.20 to 0.16 W/m²K, window targets from 1.4 to 1.2 W/m²K (new-build notional). The notional dwelling target (SAP compliance benchmark) uses 0.18 for walls, 0.11 for roofs and 0.13 for floors; the roof value tightened from 0.13 in 2013, while the wall and floor notional values carried over. The biggest changes were to the carbon emission factors and the introduction of the Primary Energy Rate (TPER) as an additional compliance metric alongside carbon emissions.
A typical cavity wall construction to achieve 0.18 W/m²K would use: brick outer leaf, 150 mm full-fill mineral wool cavity insulation (lambda 0.032-0.034), 100 mm aerated concrete block inner leaf (lambda 0.11), 12.5 mm plasterboard on dabs. Alternative constructions include partial fill PIR insulation (100 mm with a 50 mm residual cavity) or timber frame with 140 mm mineral wool between studs plus a service void.
No. These are specifically for England under Approved Document L 2021. Scotland has Section 6 of the Building Standards (generally stricter), Wales has its own Part L (broadly similar but with some differences), and Northern Ireland has Part F (Conservation of Fuel and Power). Always check the specific regulations for the country where you are building.