TradeCalculator.co.uk
Heat Pump Radiator Calculator
Re-size radiators for heat pump flow temperatures. Apply BS EN 442 de-rating factors to existing radiator output at a 45°C heat-pump flow vs the 75°C gas-boiler rating condition.
From room-by-room heat loss calc
Rated output at delta-T 50C
For total deficit estimate
Default 20°C = BS EN 442 reference (living room 21°C, bathroom 22°C, bedrooms 18°C per BS EN 12831)
HP typically 5C
Next up: related pages
How We Calculate This
This calculator applies the BS EN 442 de-rating factors to your existing radiator output to determine if they are adequate for heat pump flow temperatures.
De-rating factors (% of rated output)
At the default 5K heat-pump return spread and a 20°C room (the BS EN 442 reference room temperature):
- 35°C flow: ~16% of rated output (ΔTm ≈ 12.5K)
- 40°C flow: ~26% of rated output (ΔTm ≈ 17.5K)
- 45°C flow: ~35% of rated output (ΔTm ≈ 22.5K)
- 50°C flow: ~46% of rated output (ΔTm ≈ 27.5K)
- 55°C flow: ~57% of rated output (ΔTm ≈ 32.5K)
Raising the design room temperature lowers ΔTm and so reduces these factors; the calculator recomputes them live for the room temperature and return spread you enter.
Frequently Asked Questions
Radiators are rated at a standard ΔT of 50K (BS EN 442 reference condition: flow 75°C, return 65°C, room 20°C). Heat pumps operate at much lower flow temperatures (35–45°C), which dramatically reduces radiator output. At 45°C flow with a typical 5K heat-pump return spread and a 20°C room, a radiator produces approximately 35% of its BS EN 442 rated output (mean water 42.5°C, so ΔTm ≈ 22.5K, factor = (22.5/50)^1.3 ≈ 0.35).
The de-rating factor is the proportion of a radiator’s rated output available at the heat pump flow temperature. It is computed live from (ΔTm/50)^1.3 per BS EN 442, with a default 5K return spread and a 20°C room. Typical values at those defaults: 35°C flow ≈ 0.16, 40°C ≈ 0.26, 45°C ≈ 0.35, 50°C ≈ 0.46, 55°C ≈ 0.57. So a 1000W rated radiator produces only about 354W at 45°C flow.
Not always. If your existing radiators were originally oversized for the rooms (common in older installations), they may still provide adequate output at lower flow temperatures. Radiators in well-insulated rooms with low heat loss are also more likely to be adequate.
For heat pump systems, Type 22 (double panel, double convector) or Type 33 (triple panel) radiators provide the most output for their footprint. Fan-assisted convectors are also excellent as they force air across the fins, significantly boosting output at low flow temperatures.
Yes, but higher flow temperatures reduce heat pump COP (coefficient of performance). As a rough guide, an ASHP loses roughly 0.4–0.5 COP points for every 10°C rise in flow temperature, so running cooler is always more efficient. For example, MCS product-database testing of one model showed a COP of about 4.1 at 35°C flow falling to about 3.3 at 55°C; exact figures vary widely by model and outdoor temperature, so check the manufacturer’s SCOP/COP data for your unit. It is generally better to upsize radiators than to increase flow temperature.
Related Calculators
Was this calculator helpful?
Last updated: June 2026
Verified against UK standards · estimates only, confirm with your supplier.