Determine fire safety requirements for habitable basements per Approved Document B Vol 1 (para 2.16) including protected stairways, fire doorset ratings, smoke detection, and escape windows.
Total basement floor area
Separate rooms in the basement
For an escape window/door provision (AD B para 2.10)
Doors on protected stairway route
Leave blank for an indicative automatic estimate
Next up: related pages
How We Calculate This
This calculator determines fire safety requirements for habitable basements per Approved Document B (Fire Safety) of the Building Regulations. Basement fire safety is critical because escape is upward, against the natural direction of smoke and fire spread.
Key requirements
Protected stairway: A fire-rated enclosure providing escape from basement to final exit. Required for all habitable basements.
Fire doorsets: minimum E 20 (FD20) at all openings to the protected stairway in a single family house (AD B Vol 1 Table C1 item 11b, which item 4a expressly excepts from its E 30 Sa line). No cold smoke seal and no self-closing device required within a dwellinghouse (Appendix C para C5c). FD20 doorsets are no longer certified as products, so an FD30 door with intumescent strips is fitted to satisfy the E 20 minimum.
Detection: Interlinked smoke detection on every level — minimum Grade D2 Category LD3 to BS 5839-6 (mains powered with a user-replaceable standby battery). Heat/multi-sensor detectors in kitchen areas. A basement conversion commonly warrants an upgrade to LD2 / Grade D1 (sealed, tamper-proof non-user-replaceable battery) as good practice.
The two equivalent options (para 2.16): AD B Vol 1 does not set a travel-distance limit for a house basement. Where a basement storey contains any habitable room, it must have either an emergency escape window or external door from the basement (meeting the para 2.10 escape-window dimensions), or a protected stairway (para 2.5a, REI 30 enclosure) leading from the basement to a final exit. Below-ground rooms typically rely on the protected stairway because an escape window is only an option where the basement has a suitable opening at or above ground (e.g. via a lightwell).
Frequently Asked Questions
Approved Document B Volume 1 para 2.16 requires that where a basement storey contains any habitable room, it is provided with EITHER (a) an emergency escape window or external door providing escape from the basement (per para 2.10), OR (b) a protected stairway (para 2.5a) leading from the basement to a final exit. These are equivalent alternatives. In practice a basement bedroom is usually served by a protected stairway (REI 30 enclosure with minimum E 20 (FD20) fire doorsets, which in a single family house need no cold smoke seal and no self-closing device), with interlinked smoke detection on each level and fire separation between the basement and ground floor. An escape window/door via a lightwell can satisfy option (a) where the opening meets the para 2.10 dimensions.
A protected stairway is an enclosed staircase that provides a safe route from the basement to a final exit (external door). The enclosure must have 30-minute fire resistance (REI 30), with minimum E 20 (FD20) fire doorsets at each level. AD B Vol 1 Table C1 item 11(b) rates a door forming part of the enclosures to a protected stairway in a single family dwellinghouse at E 20, and the E 30 Sa (FD30S) line at item 4a expressly excepts that case, so no cold smoke seal is required; Appendix C para C5c also exempts fire doorsets within a dwellinghouse from self-closing devices. FD20 doorsets are no longer certified as products, so in practice an FD30 door is fitted to satisfy the E 20 minimum. No habitable room should open directly onto the protected stairway without a fire doorset. This is the primary means of escape for most basements.
Not necessarily. AD B Vol 1 para 2.16 gives two equivalent alternatives: an emergency escape window/external door from the basement, OR a protected stairway to a final exit. An escape window via a lightwell satisfies the window/door option only if it meets para 2.10: an unobstructed openable area of at least 0.33m², at least 450mm high and 450mm wide, with the bottom of the openable area no more than 1100mm above the floor, and the lightwell sized so a person can exit and reach safety. If you instead provide a protected stairway, an escape window is not separately required by para 2.16 — though a second means of escape from a basement bedroom is good practice.
In a single family house the minimum is E 20 (FD20) fire doorsets at: the head of the basement stairs, any opening from the basement stairway to habitable rooms, and between the basement and ground floor level. AD B Vol 1 Table C1 item 11(b) sets E 20 for doors forming part of the enclosures to a protected stairway in a single family dwellinghouse, and the E 30 Sa (FD30S) entry at item 4a expressly excepts that case, so a cold smoke seal is not required. Self-closing devices are not required on fire doorsets within a dwellinghouse (Appendix C para C5c), although some building control bodies still recommend a closer on a basement stair door. The door that does need FD30S with a self-closer is a door between the house and an integral garage (Table C1 item 11a). Because FD20 doorsets are no longer certified as products, an FD30 door fitted with intumescent strips is what you buy to meet the E 20 minimum.
The AD B Vol 1 minimum for a new dwelling is a Grade D2 Category LD3 system to BS 5839-6 — interlinked mains-powered alarms with a user-replaceable integral standby battery, covering the circulation spaces that form the escape routes on every level (e.g. basement, each landing). For a basement conversion or a basement bedroom, good practice is commonly to upgrade to Category LD2 (adding a detector in the principal habitable room and high-risk rooms) and to Grade D1, which uses a sealed, tamper-proof, non-user-replaceable (long-life) standby battery, with heat/multi-sensor detectors in kitchens. Detector positions are placement-based per BS 5839-6, not a fixed floor-area divisor.