Fire Escape Distance Calculator

Check travel distances to fire exits against Approved Document B maximum limits. Calculate compliance for one-direction and two-direction escape routes.

Measured along the actual path of travel

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator checks the actual travel distance against the maximum limits in Approved Document B Volume 2, Table 2.1 (buildings other than dwellings) and Approved Document B Volume 1 (within and around flats).

Maximum distances

The limit depends on the building use and whether escape is possible in one or more than one direction.

  • One direction (dead end): 9–25m depending on building use
  • More than one direction: 18–45m depending on building use
  • Office / shop / assembly (elsewhere): 18m / 45m
  • Industrial & storage: 25m / 45m (normal hazard); 12m / 25m (higher hazard)
  • Within a flat: 9m to the flat entrance door (AD B Vol 1 para 3.18 b(i), Diagram 3.3)
  • Common areas of flats: 7.5m / 30m (AD B Vol 1 Table 3.1)
  • Inner rooms: limited to the one-direction Table 2.1 figure for the use (AD B para 2.11e)

Travel distances in Approved Document B are fixed limits — they are not extended where a sprinkler system is fitted. A sprinkler-based extension of travel distance is only available through a BS 9999 risk-engineered assessment by a competent fire engineer.