TradeCalculator.co.uk
External Fire Spread Calculator
Check unprotected areas against boundary distance per Approved Document B Vol 1 — Method 1 (Diagram 11.7, m² limit for small residential buildings) or Method 2 (Table 11.1, % limit).
Perpendicular distance from the facade to the relevant boundary (simple methods apply only at ≥1m — AD B para 11.16)
Width of the rectangle enclosing all unprotected areas
Height of the enclosing rectangle (Method 1 ≈3 storeys, Method 2 ≤10m)
Total unprotected openings in the facade
Average area of each unprotected opening
To Appendix E — AD B para 11.21 lets you double the permitted unprotected area (or halve the boundary distance, min 1m)
Override: enter a known unprotected % directly instead of windows × area
Safety notice
Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.
Next up: related pages
How We Calculate This
This calculator applies the two simple methods in Approved Document B Vol 1 (paragraphs 11.16–11.21) to check whether the unprotected area on a facade complies with the boundary distance requirements. Both methods apply only to walls a minimum of 1m (1000mm) from the relevant boundary.
Method 1 — Diagram 11.7 (residential)
- Who: small residential buildings — flats and dwellinghouses up to 3 storeys (excluding basements) or 24m per side.
- Limit: an absolute maximum unprotected AREA in m² — 5.6 m² at 1m, 12 m² at 2m, 18 m² at 3m, 24 m² at 4m, 30 m² at 5m, no limit at 6m or more (interpolate between values).
Method 2 — Table 11.1 (other small buildings)
- Who: buildings or compartments up to 10m high for which Method 1 is not appropriate.
- Enclosing rectangle: width × height of the smallest rectangle enclosing all unprotected areas.
- Unprotected percentage: total unprotected area ÷ enclosing rectangle area × 100.
- Table 11.1 lookup: maximum permitted PERCENTAGE by boundary distance (4% under 1m; 8% at 1m, 20% at 2.5m, 40% at 5m, 60% at 7.5m, 80% at 10m, 100% at 12.5m — interpolate).
Sprinklers (para 11.21): a system to Appendix E lets you double the permitted unprotected area, or halve the boundary distance (minimum 1m). For taller buildings or precise design, use the full BR 187 enclosing-rectangle procedure. The Table 11.1 percentages are not adjusted by purpose group — that distinction (84 vs 168 kW/m² radiation in para 11.16) only affects a full BR 187 calculation.
Frequently Asked Questions
AD B Vol 1 paragraph 11.16 gives two simple methods for walls at least 1m (1000mm) from the relevant boundary. Method 1 (Diagram 11.7) applies to small residential buildings — blocks of flats and dwellinghouses up to 3 storeys (excluding basements) or 24m per side — and sets an absolute maximum unprotected AREA in m²: 5.6 m² at 1m, 12 m² at 2m, 18 m² at 3m, 24 m² at 4m, 30 m² at 5m, and no limit at 6m or more. Method 2 (Table 11.1) is for other small buildings or compartments up to 10m high and uses a PERCENTAGE of the enclosing rectangle: 4% under 1m, 8% at 1m, 20% at 2.5m, 40% at 5m, rising to 100% at 12.5m. This calculator picks Method 1 for flats and dwellinghouses (purpose group 1, the only buildings para 11.17 assigns to Diagram 11.7) and Method 2 for all other buildings, including institutional and residential-other (purpose group 2). For taller buildings or precise design, use the full BR 187 enclosing-rectangle procedure.
For Method 2 (Table 11.1) you draw the smallest rectangle that encloses all unprotected areas on a facade, divide the total unprotected area by the area of that rectangle and multiply by 100 to get the unprotected percentage, then compare it against the maximum permitted percentage for the distance to the relevant boundary (4% under 1m rising linearly to 100% at 12.5m, interpolating between table values). The boundary distance is measured perpendicular from the facade to the site boundary or the centre line of an adjoining road, railway or canal. Method 2 is used where the residential Method 1 (Diagram 11.7) is not appropriate, and applies up to 10m building height.
An unprotected area is any part of an external wall that does not achieve the required fire resistance for the building. This includes windows (unless fire-rated glazing), doors, openings, and wall panels that do not meet the fire resistance standard. Areas of wall with less than the required fire resistance from the inside (EI rating) are also unprotected. Small unprotected areas under 1m² and more than 1.5m from any other unprotected area may be disregarded.
Where a building is fitted throughout with an automatic sprinkler system, AD B Vol 1 paragraph 11.21 allows you to either double the permitted unprotected area, or halve the boundary distance (to a minimum of 1m). In practice this means roughly double the unprotected area at the same distance, or the same area at a shorter distance. The system must be designed and installed in accordance with AD B Appendix E — BS 9251 for residential buildings, or BS EN 12845 for non-residential buildings (or residential buildings outside the scope of BS 9251).
The two simple methods in AD B Vol 1 only apply to walls a minimum of 1m (1000mm) from any point on the relevant boundary (paragraph 11.16). Below 1m, neither Method 1 nor Method 2 applies: the wall must be fire-resisting from both sides and only the small unprotected areas allowed by Diagram 11.5 are permitted (paragraph 11.8). At 1m without sprinklers, Method 2 permits about 8% unprotected area, or Method 1 permits 5.6 m² for a small residential building. The relevant boundary includes the site boundary, the centre line of a road, railway or canal, or a notional boundary between two buildings on the same site (AD B treats the distance to a notional boundary the same as to a relevant boundary).
Yes, fire-resistant glazing that achieves the required EI (integrity and insulation) rating for the building is treated as protected area and does not count as unprotected. E-only rated glazing (integrity only, such as Georgian wired glass) still counts as unprotected area because it does not prevent radiant heat transfer. Using EI-rated glazing is a common solution when boundary distances are tight.